Available Sessions

PTTV_SCHED.png

ABOUT THE POWERTEST TV PREMIUM REGISTRATION PACKAGE

Premium PowerTest TV registration includes approximately 48 hours of technical content eligible for up to 48 NETA CTD credits or 4.8 CEUs. All PowerTest TV content will be made available for on-demand viewing and will remain accessible to attendees through June 30, 2022.
Please note that all presentations are eligible for 1 CTD/.1 CEU unless noted in the listing as a seminar (4 CTDs/.4 CEUs). Additionally, to earn industry credits for a virtual session, presentations must be viewed in its entirety. 
Register Now


PTTV_SCHED.png
  • The PowerTest 2022 Keynote Presentation
hester_speaker_photo.pngPRESENTED BY
Robert Bryce


Robert Bryce is a Texas-based author, journalist, podcaster, film producer, and public speaker.  Over the past three decades, his articles have appeared in numerous publications including the Wall Street Journal, New York Times, National Review, Field & Stream, and Austin Chronicle.

Bryce has given nearly 400 invited or keynote lectures to dozens of groups including the Marine Corps War College, Sydney Institute, Jadavpur University, Northwestern University, and a wide variety of professional associations and corporations. He has also appeared on dozens of TV and radio shows including NPR, BBC, MSNBC, Fox, Al Jazeera, CNN, and PBS.

  • Arc Flash Hazards: The Benefits of Primary Injection Testing
hester_speaker_photo.pngPRESENTED BY
Glen Wahl
Megger

The purpose of this paper is to discuss the importance of primary injection testing and its impact on Arc Flash Hazard mitigation. Current Arc Flash labeling requirements often rely upon an electrical system’s protection coordination in order to operate correctly. The proper testing of a system at high current levels is a critical step to ensuring the system will operate in a safe and effective manner in the event of a fault. Primary injection testing should be a component of any electrical maintenance program.

 

  • Cyber Security: the Effect on NETA Companies, Safety Program, and Clients and How to Respond Now and in the Future (Seminar)

hester_speaker_photo.pngPRESENTED BY
Matthew Ellis
Sentinel Field Services, LLC

 

As technology proliferates in the workplace, in the field, and into every aspect of our daily lives, so does the liability and risk elements involved with properly harnessing technologies and safely utilizing networks, computer resources, and infrastructure. Cyber security has become a concern for everyone: from our home lives to our workplace, our customer sites, their compliance groups, and all the way up to international governments. New compliance standards, insurance requirements, client requirements, contract amendments, and a host of new and necessary practices are proliferating and evolving to combat the future of cyber-attacks, information theft, and cyber terrorism. This Seminar intends to educate everyone from any background on those practices: how cyber security works, how hackers and criminals operate in the cyber realm, and how to identify and expect the upcoming changes in contracts and site work, the changes in compliance group requirements, the governance and use of industrial facility networked equipment, and how to harden workstations and servers within the company while providing security to any employee that is on site, at their home base, in their personal home office, and beyond to meet compliance standards set forth by customers and contracts.

  • Developing an Electrical Workforce (Seminar)

hester_speaker_photo.pngPRESENTED BY
Tom Sandri
Protec Equipment Resources

 

In this seminar we will focus on developing skills and knowledge as it applies to an electrical workforce, workforce development strategy, the benefits of workforce development, elements of workforce development and how it differs from workplace training.  We will explore the paradigm shift from in-person classroom to online, virtual, and blended training.  We will address obstacles and challenges along with the Universal Design for Learning (UDL) educational framework and set of principles for maximizing learning opportunities.  And finally, we will review the pre and post pandemic electrical safety training paradigms to get a better glimpse of what the future holds.

  • Electrical Testing and Maintenance of Rotating Machines (Seminar)

hester_speaker_photo.pngPRESENTED BY
Abel Gonzalez and Sameer Kulkarni
Megger

 

The condition of a rotating machine can be evaluated by using a combination of Static and Dynamic testing techniques. Static tests are performed while the motor is disconnected from the system, typically during manufacturing, commissioning, maintenance, or repairs. The goal of Static tests is to provide a proper picture of electrical characteristics of the machine.

As part of Static tests, the status of windings is evaluated by measuring parameters such as resistance, inductance, and impedance. In certain situations, winding impedance is measured at different rotor positions by performing the rotor influence check test. This test is utilized to verify the uniformity of the air gap between the rotor and the stator. Deviations between winding parameters could indicate manufacturing defects, contact resistance issues and, turn to turn faults. The turn-to-turn insulation, which is both the weakest spot and the place where most of the insulation failures begin in a motor, is also evaluated during Static testing using voltage Surge tests. During Surge tests, voltage pulses are injected into the machine windings to simulate the startup process, where a nonlinear voltage distribution exists across the winding. The results of this can be used to diagnose the condition of the machine insulation system and when trended over time be used to plan machine replacement or overhaul.

The status of the ground wall insulation system is evaluated by high voltage DC tests that include tests such as Insulation Resistance, Polarization Index, Dielectric Absorption Ratio, Step Voltage, Ramp, Dielectric Discharge, and Dielectric Voltage Withstand (hipot). Other types of Static tests include the application of high voltage AC to measure the insulation’s power and dissipation factors. In some cases, low frequency AC tests, known as VLF tests, are used to test rotating machine insulation with the advantage of reduced power requirements of test equipment.

This seminar will cover the theory behind each of the different static tests used to evaluate the status of the winding and the insulation of rotating machines. It will discuss best practices, applicable standards as well as the criteria used to analyze the condition of rotating machines.

  • Frequency-Based Diagnostic Testing of Power Transformers (Seminar)

hester_speaker_photo.pngPRESENTED BY
Dinesh Chhajer and Diego Robalino
Megger

 

In the last 20 years frequency response analysis for condition assessment of electro-mechanical and dielectric condition of power transformers has been implemented in the field and factory. International standards and technical guidelines are readily available for end users to educate themselves on the theory and applications of each specific method.

For this seminar, presenters will focus on the best practices to perform Sweep Frequency Response Analysis (SFRA) and Dielectric Frequency Response (DFR) testing in field and factory. Through case studies the agenda will cover main applications and interpretation of results of advanced frequency-based diagnostic techniques, namely SFRA and DFR.

According to the latest revision of IEEE C57.149 and IEC 60076-18, the most common SFRA tests to be performed on a transformer are open circuit and short circuit tests. Nevertheless, inter-winding inductive and capacitive tests are also available and recommended for commissioning. The highlighted best practices in both standards will be discussed to avoid measurement error and/or discrepancies against reference measurements. This seminar will give an insight on the procedure to follow if no baseline or reference measurements are available. Failure modes explained in different standards would be explained through real life case studies. 

On the dielectric side, IEEE C57.152 and IEEE C57.161 provide the fundamentals for the application and interpretation of DFR results obtained in the field and factory. Although, different factors may affect the measurements including but not limited to secure connection, insulation temperature, frequency range and surrounding EMI in the location where tests are performed. Therefore, specific guidelines and best practices will be discussed by applications on transformers, bushings and instrument transformers. 

The seminar will cover fundamentals, theory, best practices, case studies and interpretation on the use of advanced frequency-based diagnostic techniques SFRA and DFR to assess the overall transformer electro-mechanical and dielectric condition. 

  • Hands-On Battery Maintenance and Testing (Seminar)

hester_speaker_photo.pngPRESENTED BY
Tom Sandri
Protec Equipment Resources

 

Batteries are used for a wide variety of services throughout technology today. To begin to study battery operation and characteristics, a few terms that are used with batteries must be understood. Next, we must understand that a battery converts chemical energy to electrical energy. This conversion enables electrical power to be stored. Once the basic theory behind the operation of batteries is understood, we can apply these concepts to better understand the way batteries are utilized. This training seminar will introduce learners to stationary batteries and the maintenance and testing they require. The participants will learn to identify various types of batteries, their construction and applications. Learners will define safety and hazards related to batteries and testing. We will look at various failure modes related to batteries and how to identify each failure. Tests and inspection procedures will be explained along with the interpretation of test results.

  • Hazardous Energy Control – Common Pitfalls & How to Mitigate
hester_speaker_photo.pngPRESENTED BY
Jeremy Presnal
Shermco Industries

How often do you hear “we are using the clients energy control (e.g. LOTO) process?” Arguably, many host employers have effective processes that reflect the required compliance elements, capture relative risk and controls necessary to protect service industry employees.  However, what happens when this is not the case?  What is required from a compliance standpoint (e.g. OSHA, NFPA 70E, etc.)?  What process and tools need to be in place, as well as how should the team respond?  Who has decision rights to approve a deviation from company policy? These are all questions that Shermco Industries has grappled with over the past 2 years on our Drive For Excellence journey targeting Hazardous Energy Control Enhancements. This presentation will explain critical learnings and suggestions for avoiding common pitfalls with regards to host / service industry specific to management of hazardous energy control.

  • Help, My Customer is Asking About “Digital Substation” Testing!  What is This About, What do I Need to Know, and What Equipment do I Need to Test it? (Seminar)

hester_speaker_photo.pngPRESENTED BY
Scott Cooper
OMICRON electronics Corp. USA

 

Digital relays continue to revolutionize relay protection by increasing sensitivity, security, and near-term reliability.  The next step in this revolution is the digital substation which, in simplest terms, replaces copper protection and control wiring with devices that communicate using a specialized protocol via an ethernet network.  Of course, this new type of substation requires new knowledge as well as specialized tools to commission, test and troubleshoot them. 

This 4-hour seminar will provide an introduction to IEC 61850 including:
1.Client Server, GOOSE, and Sampled Values communication overview
2.The standard configuration file types
3.Ethernet network overview and IEC 61850 message structure
4.Cyber security of the digital substation
5.How 61850 can influence the operation of the protection and control system
6.How 61850 can influence the testing of the substation
7.Digital substation testing overview including isolation, test methods, and test plans
8.Client Server testing and testing tools
9.GOOSE messaging testing and testing tools
10.Sampled Values testing and testing tools
11.Specialized IEC 61850 network testing and testing tools

  • Inspiring Team Members to do ‘Right’ Things in ‘Right’ Ways (Even When No One’s Watching) (Seminar)

hester_speaker_photo.pngPRESENTED BY
Tim Autrey
PPI Global

 

This presentation will cover:

  • Compliance vs Desire: An interactive in-classroom scenario will be used in which the participants will identify for themselves how they behave in conditions/cultures of compliance.
  • Environment is Stronger Than Will: An interactive exercise will be used to demonstrate how environment can break even the strongest sense of ‘will’ of most individuals. This is important insight for leaders at any level because within an organization, leaders are the predominant creators of the work environment.
  • The Individual Performance Model: A simple model of human behavior from external input/stimulation to thoughts, feelings, choices, actions, and behaviors. Understanding and learning to apply this model greatly increases one’s ability to influence others.
  • Primary Performance Needs: When this insight is paired with the Individual Performance Model™ and properly utilized, a leader/influencer can inspire virtually any person to do virtually…anything. Participants will be provided with access to the PPI Primary Performance Needs App, which will allow them to identify their own primary performance needs.
  • Your Sphere of Influence: Coming ‘full circle’, the session now draws back to behaviors in ‘compliance-based’ vs ‘desire-based’ environments and how to use this insight to LEAD toward an environment/culture of one team with one goal having one conversation.
  • Invisible Injury Sequela

hester_speaker_photo.pngPRESENTED BY
Terry Becker
TW Becker Electrical Safety Consulting, Inc.

 

The electric shock hazard has been accepted by Journeyman Electricians as part of the job, a right of passage.  Shock injuries have not been reported.  If they have been reported they were fatalities.  The American Electrician’s Handbook from 1942 to 1960 taught electrical workers to use their bodies as voltage detectors.  All of this was and is unacceptable.

Electrical injury statistics from multiple sources in Canada and the USA clearly indicate that electric shock injuries and fatalities are still occurring at an alarming high rate.  Thousands of shocks are still not reported.

Shock is an invisible injury to electrical workers.  Short term immediate effects are well known and documented.  The long-term effects related to shock sequela have been discussed but have not been a priority, Doctors cannot study what is not reported.  Sequela is real, but electrical workers are not aware.  The long-term effects can be psychological, neurological, and physical.  Two research centres have placed focused on sequela from shock, the St. Johns Rehab Electrical Injury Program in Ontario, Canada and the University of Chicago, Chicago Electrical Trauma Rehabilitation Institute (CETRI), but their efforts have limited notoriety.

John Knoll is a Journeyman Electrician, a Professional Electrical Contractor from Edmonton, Alberta and has been impacted by sequela related to multiple shock injuries in his career.  An overview of the sequela due to shock, the efforts of the two institutes related to researching and treating the sequela and John’s story will be presented

  • Near-Misses and Your Safety Program: Are You Really a Learning Organization?

hester_speaker_photo.pngPRESENTED BY
Stephen Hester
Saber Power Field Services, LLC

The old cliché “No harm, no foul” may work on the ball field but it is a dangerous rule to live by, especially around electrical hazards. Statistics show that for every fatal accident there many risky behaviors that do not result in injuries and may go unnoticed. OSHA defines a near miss as “an incident in which a worker might have been hurt if the circumstances had been slightly different.” It may take only a little change in circumstances for an unsafe act to become a fatal one. Investigations into near misses often focus on employee behavior and not the actual reasons why the behavior occurred. Near misses are often not reported and when they are, rigid safety rules may result in adverse action such as suspension or termination. When near misses go unexamined, organizations lose the ability to learn the lessons and to train their employees so that the risky behaviors do not happen again. Organizations need to change the way they leaders, managers, supervisors and field employees think about near misses and their potential effects. This presentation examines current practices in near miss reporting and investigation, looks at causation, and discusses way in which organizations can improve their near-miss reporting programs, change their reactions to near misses, and improve their safety culture.

  • Primer on Transformer Diagnostic Testing (Seminar)

hester_speaker_photo.pngPRESENTED BY
Brandon Dupuis and Charles Sweetser
OMICRON electronics Corp. USA


Transformers are the largest, most expensive, and highly critical components of most utility substations.  In order to ensure a long, useful service life, it is critical that a power transformer and its ancillary components are tested regularly for incipient fault modes.  The seminar focuses on the diagnostic testing that can, and should, be performed during regular maintenance intervals, to ensure that the transformer is in good condition, and is capable of continuing its in-service duty with minimal risk.  The following electrical transformer diagnostic tests will be discussed:

•Overall Power Factor
•Exciting Current
•Turns-Ratio (TTR)
•Leakage Reactance (Short-Circuit Impedance)
•Sweep Frequency Response Analysis (SFRA)
•DC Winding Resistance

  • Safety Performance and the Correlation to Corporate Profitability

hester_speaker_photo.pngPRESENTED BY
Kenneth Peterson
Hampton Tedder Technical Services

A decrease in the frequency of Occupational Safety and Health Administration (OSHA) Recordable injury incidents will result in an inverse correlation of increasing corporate profitability as a contractor in the high voltage utility sector.

  • Testing and Commissioning of Instrument Transformer in The Field (Seminar)

hester_speaker_photo.pngPRESENTED BY
Morteza Talebi
TRC Companies

Instrument transformers measure and transform high current and voltage magnitudes in the transmission and distribution system to low and more manageable secondary magnitudes that are used to supply intelligence to metering, monitoring, and protective control equipment.

The purpose of this training is to provide a general overview of instrument transformers and the required tests for ensuring the serviceability of substation current transformers and voltage transformers. Topics include Current and Voltage Transformer theory and application, nameplate interpretation, current and potential transformer stand alone and circuit testing and precautions in field testing of Instrument transformers.

  • Transformer Testing Theory and Case Studies (Seminar)

hester_speaker_photo.pngPRESENTED BY
Mike Anderson
Doble Engineering Company


Why are we testing? What do the results mean? What do they tell us about the apparatus? When testing transformers, a working knowledge of the theory behind the measurement is critical to understanding and interpreting the results. This understanding enables the tester to identify potential setup problems, test equipment issues, environmental impacts, and troubleshooting steps necessary in order to ultimately make a smart decision regarding the health of the transformer. This seminar will briefly review the theory and data interpretation of common transformer tests, including dielectric, excitation, turns ratio, and winding resistance, then shifting to the presentation of real-world case studies, providing examples of both fault and non-fault related issues that can impact test data.

  • Vacuum Interrupter Test and Conditioning (Seminar)

hester_speaker_photo.pngPRESENTED BY
Finley Ledbetter
Group CBS, Inc.


Medium voltage power equipment has been controlled by interrupters of all types for the last 100 years. Since 1920, engineers and scientists have been working to develop and refine the vacuum interrupter as the interrupting method of choice. Without a proven new technology on the horizon, today vacuum interrupter (VI) must stay the focus for all designs and types of interrupting equipment. The wear dynamic and life of the vacuum interrupter make it an ideal replacement for the air, oil, and gas interrupters that we all used with great success until the refinement of the VI.  The property that makes it a cost efficient and technologically superior method to interrupt an arc also makes it a maintenance nightmare to those who must rely on it. Consider a sealed envelope with a set of contacts inside that you cannot see, touch, or easily determine if it will perform as required when needed. That has been both the advantage and disadvantage compared to other types of interrupters. In this workshop, we’ll discuss and show hands-on the methods for determining if this small, yet dynamically important piece of your power distribution system, is healthy and ready to perform for another 5 plus years.  Or if it needs to be replaced or watched very closely in the future.

PTTV_SCHED.png


PTTV_SCHED.png
  • A Comparison Between Dielectric Frequency Response and Narrow Band Dielectric Frequency Response as Methods for Assessing the Insulation of Transformers and Bushings

hester_speaker_photo.pngPRESENTED BY
Sanket Bolar
Megger

Power Factor (PF) testing has been a proven method when assessing the quality of insulation systems in transformers and bushings for many years. Single frequency power factor measurements, however, provide only pass/fail criteria and little to no diagnostic information about where the problem of the insulation is and what it might be.

Techniques like Dielectric Frequency Response analysis(DFR) and Narrow Band Frequency Response(NBDFR) have been developed that use information provided by tests performed at different frequencies which allow us to obtain a much better diagnostic analysis of the insulation under evaluation DFR uses mathematical modelling tools to estimate the condition of the insulation system and analyze the solid and liquid parts of the insulation separately. DFR measurements are non-intrusive and provide onsite information about the amount of moisture present in the solid insulation.

The length of the DFR test is dictated by the lower frequency limit which, in turn, depends on the temperature of the transformer. Testing at low temperatures involves longer measurement times.

A shorter version of the DFR test, known as Narrow Band DFR, which uses information from a narrower band of frequencies allows the user to perform a quick triage of the transformer and obtain information as to whether or not the transformer’s insulation needs further evaluation or if it is fit to be put back into service.

NBDFR can be considered as a complementary solution which doesn’t rely on database modelling for moisture assessment.    NBDFR provides valuable information that a traditional line frequency PF may miss due to  power factor’s increased sensitivity to moisture at low frequencies.  

This paper will provide a comparison between DFR and NBDFR as insulation assessment tools on transformers and bushings.  A comparative analysis of the information obtained through wideband DFR  and a narrowband DFR test will be performed.  DFR and NBDFR responses from various transformers and bushings will be shown to help the reader understand, review and differentiate a questionable insulation system from a healthy one. Additional case examples will be provided to highlight the importance of NBDFR as a tool in detecting problems in bushing insulation.

  • Acceptance Testing Lessons Learned - PV Generation Sites

hester_speaker_photo.pngPRESENTED BY
David Morrisey
Asplundh Engineering Services, LLC

 

The objective of my presentation will be to discuss various challenges, lessons learned, interconnection requirements and specific test procedures we have utilized to perform testing and commissioning of PV Generation Sites across the country with various utilities.  The specific focus of the discussion will be testing at project sites which directly interconnect to utility distribution circuits ranging from 5kV – 35kV.
  • Advantages and Disadvantages of Very Low Frequency and Tan Delta Testing

hester_speaker_photo.pngPRESENTED BY
Charles Nybeck
Megger

For many years the industry accepted method for evaluating medium and high voltage power cables was DC withstand testing. However, the DC method provided little, if any, diagnostic value and could be destructive to aged cables. New developments in the technology and industry standards have led to new testing techniques utilizing AC voltage that offer more diagnostic value without the risk of damaging aged cable. These methods include Very Low Frequency (VLF) and Tan Delta testing, where each test has its own unique advantages and disadvantages. VLF is performed as a withstand test similar to the DC method, but the test is commonly performed at a frequency of 0.1 Hz. Most industry standards, including the IEEE 400, no longer recommend DC hi-pot testing of XLP and EPR cables. It states that DC hi-pot testing of service-aged XLP and EPR cables may not provide meaningful information and may be destructive. The VLF withstand test can be conducted using sinusoidal or cosine-rectangular (CR) wave forms, where CR is used to mimic cable testing at line frequency during polarity changes. However, by testing in the frequency range of 0.01 to 0.1 Hz as opposed to line frequency, the power requirement is reduced and thus allows the use of a significantly smaller and lighter test device. An alternative, or complementary, diagnostic method is the Tan Delta testing method. Tan Delta, also referred to as Loss Angle or Dissipation Factor, is a diagnostic cable testing method to evaluate the condition of the insulation. The test results provide a “global” assessment into the condition of the cables insulation. Although the Tan Delta method provides a valuable non-destructive testing alternative, there are some disadvantages. For instance, what actions should be made based on questionable test results. While the test itself is simple to perform, in many cases experience and historical data is needed to evaluate test data. This presentation will cover the advantages and disadvantages of VLF and Tan Delta cable testing techniques and how to use these tests as part of a cable maintenance program. In addition, industry standards, field challenges, and best practices for these testing techniques will be discussed, as well as recommendations to produce reliable results for historical trending purposes.

  • Assets Health Indices for Substation Equipment

hester_speaker_photo.pngPRESENTED BY
Albert Livshitz
Qualus Power Services

  • Bushing Condition Assessment: What You Don’t Know Can Really Hurt You!

hester_speaker_photo.pngPRESENTED BY
Volney Naranjo
Megger

Bushings are an integral part of transformers, high voltage circuit breakers and other power system assets. Unfortunately, surveys and studies have shown that bushings are also a big contributor to power transformer failures. Any deterioration in the insulation condition of a bushing, especially if not diagnosed at an early stage, can develop rapidly and lead to catastrophic failure of not only the bushing, but also the associated apparatus, and its ancillary devices. Capacitance and Power Factor (PF) measurements are the most common tests conducted on condenser type bushings to assess the condition of the insulation. Performing these measurements requires proper instructions and specific procedures, the operator has to be careful and avoid common mistakes while carrying out the tests as part of a predictive maintenance strategy. Shortcuts or errors in the procedures and measurements can lead to incorrect assessment of the bushing insulation condition, case in which a potential problem can go unnoticed or cause false triggers.

This paper will focus on the best testing practices to follow and the common field errors that the operator should avoid to obtain reliable and repeatable measurements, minimizing any potential and costly user introduced mistakes. Topics such as effect of temperature and humidity, correct handling of capacitance tap for C1 and C2 measurements, best use of hot collar measurements, effective grounding and shorting techniques, utilization of guard circuit to eliminate surface leakage currents, alternative troubleshooting techniques for results validations, trending and analysis of test results and assessment of overall PF measurements with bushing results will be covered. Additionally, the paper will focus on variable frequency based PF testing, a technique also known as Dielectric Frequency Response (DFR), which expands the bushing PF measurements beyond the nominal frequency and provides an advanced diagnostic tool. DFR of bushing can provide a greater insight to the user with the ability to predict the health condition and be proactive in identification of moisture, contamination and losses that may be overlooked in nominal frequency PF testing. The paper will conclude with case examples highlighting the benefits of following best testing practices. It will also provide DFR field results that help in predictive assessment of bushing insulation failure.

  • Capacitive Voltage Transformer Testing Practices and Field Challenges

hester_speaker_photo.pngPRESENTED BY
Joseph Aguirre
Megger

The correct operation of protection systems is crucial to identify and isolate fault conditions in order to maintain reliability of the power system. While relays are workhorses of these protection systems, the accurate delivery of actuating quantities (voltage and/or current) by voltage and current transformers is indispensable. In metering applications, instrument transformers assume the most significant role as they are used for revenue calculations. It is, hence, imperative to verify the integrity and functionality of such instrument transformers.

Capacitive Voltage Transformers (CVT) are often utilized in power systems to step down high voltage signals to suitable levels, for use by relaying and metering applications. Due to the nature of their application, CVTs are required to fulfill dual responsibilities of accurate signal reproduction and maintaining insulation levels to preclude faults to ground. Consequently, measurement of ratio error, phase angle deviation and polarity are important and so is testing the internal insulation of CVTs. 

This paper will concentrate on testing practices of CVTs, and common challenges experienced to be able to test the different capacitances, the transformation ratio and phase deviation, insulation of the inductive component and overall mechanical condition. Diagnostic testing techniques such as Tip up test and Narrowband dielectric frequency response will be discussed as well as the corresponding analysis of results. 

  • Comparison of AC Hipot and PD Measurements for the Commissioning of Metal-Closed Distribution Switchgear

hester_speaker_photo.pngPRESENTED BY
Mathieu Lachance
OMICRON electronics Canada

Medium voltage (MV) distribution switchgear are a critical part of almost any industrial facilities. Their main functions can include interrupting fault currents, isolating feeders or section of a distribution network and providing metering data to different processes. Because of this, the reliability of those equipment is crucial. Unfortunately, little importance has historically been given to the assessment of the insulation of complete switchgear assemblies during maintenance [1] and at commissioning.

There is only a limited number of published surveys available regarding the causes of failure in MV metal-enclosed distribution switchgear. Probably the most notable example of such survey was published in the appendices of IEEE 493-1997 and dates back from the 1970s. However, some data from a smaller survey performed in 2008 was summarized a few years ago [2] and showed very similar results, at least for the identified causes of failure. In both surveys, approximately 25% of failures were deemed to be caused by partial discharges (PD) for MV switchgear. In addition, in the original survey, approximately 20% of failures were attributed to improper handling or improper installation as the principal root cause.

Conventional partial discharge measurement is a well-established sensitive measurement to detect anomalies during routine tests for almost every medium and high-voltage electrical apparatus. For metal-enclosed switchgear, guidance is provided by IEEE Std C37.301, IEC 62271-200 and CSA C22.2 No. 31-18. However, PD measurements are deemed optional for both IEEE and IEC standard, while it is a stringent requirement for CSA for switchgear that have a rated voltage of 15kV and above. For an unknown reason, the switchgear industry seems to rely mainly on voltage withstand test to assess the insulation of complete switchgear assemblies,

Usually, at the end of the factory tests, the switchgear is disassembled and shipped to site in different sections, where it is reassembled. Once again, the usual test procedures include an insulation resistance test and an AC voltage withstand test. Unfortunately, these will only detect major defects. If PD is present in the switchgear, deterioration will occur at a fast pace in organic insulation systems. Sharp edges from questionable assemblies, subtle damages from transportation and handling in addition to objects left behind such as tools and hardware can create surface and corona discharges. While the former can lead to failure over time, the by-products of corona discharges are corrosive and will deteriorate the switchgear mechanical parts.

This paper presents the results of an experiment that was performed in collaboration with a switchgear manufacturer in order to compare the sensitivity of conventional AC hipot and partial discharge measurements to detect anomalies in complete metal enclosed switchgear assemblies. Common onsite problems were simulated, and the switchgear was tested with both an AC Hipot and a PD measurement. The results are used to expose the advantage of using conventional PD measurement during the onsite commissioning of metal enclosed switchgear.

  • Current Transformers - More Than Meets the Eye

hester_speaker_photo.pngPRESENTED BY
Will Knapek
OMICRON electronics Corp USA

 

Current Transformers are in almost every power delivery circuit.  They are often over looked and ignored during maintenance activities.  This presentation will take a look at construction, operation, and tests of current transformers.  The theory of operation and equivalent circuit will be explained.  After attending this presentation you will understand the why of each test that is normally performed on current transformers and how to interpret the results.

  • Directional Protection & Testing: Which Way is What?

hester_speaker_photo.pngPRESENTED BY
Sughosh Kuber

Megger

Directional Elements are at the core of protection schemes design and implementation helping provide secure, selective, and dependable protection systems by supervising and controlling distance and overcurrent elements.

In radial systems, conventional overcurrent relays (51/50) are sufficient to provide adequate protection from faults. However, for network systems like parallel lines or ring bus, directional overcurrent relays (67) are required to provide protection from faults. Due to the nature of these systems, an electrical fault can be seen in either the forward or reverse direction by the protective relay depending on the location of the relay in the system. Directional overcurrent relays use the direction of the power flow to provide the direction to the fault which is determined by the relay using the line impedance angle and the phase relationship between the fault current and a polarizing magnitude which can be a voltage or a current. Since directional overcurrent protection is more selective when compared to non-directional overcurrent it increases the reliability of power supply to critical loads. 

In this paper, different methods used to achieve directional overcurrent protection in electromechanical and microprocessor relays are discussed. Specifically, phase directional relay logic, ground directional relay logic, voltage polarization connections, and the calculations of test values associated with each logic and for different types of faults are discussed. Methods that use symmetrical components to achieve directional protection, in particular negative sequence directional protection, characteristics, and test values calculations are reviewed. Finally, the set of tests that need to be performed for an electromechanical directional relay as well as microprocessor based directional relay are discussed along with the testing procedure for each of those types of relays. Understanding the fundamentals of directional overcurrent protection and implementation of different methods used in directional relays will aid technicians in testing these types of relays efficiently and successfully.

  • Dos and Don'ts of Power Factor Testing

hester_speaker_photo.pngPRESENTED BY
Dinesh Chhajer
Megger

Power Factor (PF) testing has been used for more than 50 years to identify and detect insulation related problems for various electrical assets. PF test when performed correctly provides valuable diagnostic information that can be analyzed and trended throughout the life of the insulation to detect any abnormalities and dielectric failures.

The paper will talk about the best recommended field practices to perform the test effectively and obtain reliable and accurate measurements. It will focus on field aspects that can impact the measurements such as selection of correct test voltage, effect of grounding and guarding, effective measurement of insulation oil temperature and temperature correction of PF readings, position of on load tap changer, effect of humidity and bushing surface contamination, adverse effect of electrostatic interference and noise present in HV stations and most common mistakes associated with measurement of bushing C1 and C2 tests.

The paper will discuss in detail how to analyze the results by correlating other parameters obtained such as leakage current, capacitance and watts loss during PF testing. It will describe in detail what can lead to negative PF values and how external factors and environmental conditions can lead to higher than normal values. Paper will also help user understand what to do when readings don’t make sense and advanced test techniques that could be used to further diagnose and troubleshoot for informed decision making. At the end, it will share the limitations of PF test highlighting what kind of problems it cannot detect and other alternate methods available to supplement PF testing.

The paper will provide users a detailed understanding of what to do and what not to do in the field environment when performing PF testing on HV apparatus. It will complement some of the recommendations through field measurements and case studies to further drive the best field practices.

  • Dynamic Monitoring & Analysis of Substation Infrastructure using Near-Real-Time Data

hester_speaker_photo.pngPRESENTED BY
Robert Otal
METSCO

Through the introduction of online monitoring technologies in the field, including substation monitors capable of providing near-real-time data and readings on power transformers, switchgear and circuit breakers, along with line monitors for overhead conductor and monitors for underground cables, organizations now possess novel opportunities to integrate this data into their asset management frameworks such that decision-making can be enhanced.

This presentation will examine recent efforts to develop Asset Performance Management (APM) frameworks, leveraging available near-real-time data that is being retrieved from online monitoring devices. This presentation will touch upon the emerging field of analytics that can be applied to this data, including machine learning techniques, in order to detect specific signatures within the data that can be correlated to specific failure modes.

Robust APM frameworks are able to leverage this near-real-time data for the purposes of delivering dynamic health index results based upon the newest readings, as well as operational alerts that can detect possible failures that will occur in the next few weeks or months, providing organizations with enough time to take action. For complex substation assets, an APM solution can allow plant managers to manage and mitigate significant risks within their system.

This presentation will also present the results from specific case studies, where near-real-time data from field sensors was successfully leveraged and integrated into an APM such that the organization was able to enhance their risk management and asset management decision-making approaches.

  • Equipment Reliability: How Do You Get It and Keep It?

hester_speaker_photo.pngPRESENTED BY
Stephen Hester
Saber Power Field Services, LLC

Since the earliest days of the electrical industry both employers and employees have sought to identify electrical hazards and determine the best way to control them. This resulted in a cookie-cutter approach to electrical safety issues where the presence of a hazard resulted in the employment of uniform procedures. The hazard analysis concept has been formalized into a process used throughout the industry. The problem is that a hazard assessment by itself is not sufficient and may result in the selection of inadequate or incorrect control measures. The inclusion of risk in the 2015 edition of the NFPA 70E introduced another way to think about electrical hazard assessments as well as how we should conduct them. There is more to risk management than identifying hazards and choosing personal protective equipment. This paper will discuss the importance of understanding how hazards and risk differ, the importance of properly assessing risk, and the factors that influence our perception of risk.

  • Field Assessment of Rotating Machine Insulation Using DC and AC Test Methods

hester_speaker_photo.pngPRESENTED BY
Abel Gonzales
Megger

The condition of the insulation of rotating machines is evaluated by performing high voltage tests typically during manufacturing, commissioning, maintenance, or repairs. These tests are typically referred to as static tests because they are performed while the machine is offline.

High voltage DC tests are used to evaluate the status of the ground wall insulation system with tests such as insulation resistance, polarization index, dielectric absorption ratio, step voltage, and dielectric voltage withstand tests (hipot). Other types of Static tests include application of high voltage AC to verify the dielectric withstand ability of the ground wall insulation or the measurement of the insulation’s power and dissipation factors. AC tests performed at low frequencies, known as VLF tests, are used in some cases to reduce the power requirements of test equipment while still providing accurate representation of the condition of motor insulation.

The paper will discuss the principles behind each of the different static tests used to evaluate the status of the insulation of rotating machines. The evaluation criteria used to determine the pass or fail outcome of each test will be reviewed along with best practices, applicable standards, benefits and challenges of each testing technique.

  • How Do You Know Who is Qualified and Who Isn't When It Comes to Electrical Safety?

hester_speaker_photo.pngPRESENTED BY
Tom Sandri
Protec Equipment Resources

This presentation will show attendees how to use data and analytics to support asset management business decisions. Should you rent or purchase equipment? When should you sell used equipment? Learn some of the tools, methods and data points that Protec uses to answer these questions and more.

Learning Objectives:
--Understand tools and software available for asset management
--Learn what Yield and Utilization reports are, how they are created and how to use them for analysis
--Condition assessment and determining BER (Beyond Economic Repair)
--Better budgeting and risk management
--How to use this information to better negotiate with banks, vendors and manufacturers

  • Natural Ester Filled Transformers for Renewable Energy

hester_speaker_photo.pnghester_speaker_photo.pngPRESENTED BY
Karl Jakob and Alan Sbravati
Cargill Bioindustrial-Dielectric Solutions

 

The share of renewable energy in the generation matrix has been increasing significantly over the years, and a further acceleration is expected for the near future. While bringing several advantages, they are also associated with some specific requirements.  Often located in environmentally sensitive areas and subjected to cost reduction initiatives renewable generation can have demanding sustainability requirements. Not always properly filtered, several types of dielectric stresses that may not be well represented by the traditional wave shape test protocols (impulse full wave / chopped wave / switching) can produce variation in generation pattern and high content of harmonics.

Offering much more than fire safety and environmental benefits, the use of natural ester as the insulating liquid for step-up and interconnecting transformers can help in several areas. Our presentation will discuss and provide examples on:
Increased grid resiliency
     - Effective transformer and fleet design
     - Significantly improved fire safety
     - Reduced environmental Impact
     - Condition Based Maintenance Parameters
  • Online Partial Discharge Testing for Fun and Profit

hester_speaker_photo.pngPRESENTED BY
William Higinbotham
EA Technology, LLC

Partial Discharge Testing is Fun:
-Finding problems before they fail is fun.
-Solving customer problems is fun.
-Being able to diagnose issues without taking equipment out of service is fun.
-Being able to disprove the myths and misconceptions is fun.
But if we want to keep having this fun, we’re going to have to make money at it!
Hopefully this presentation will help.

  • Partial Discharge of Electrical Assets: What Are My Options and What Value Does It Provide?

hester_speaker_photo.pngPRESENTED BY
Charles Nybeck
Megger

Every high voltage (HV) asset in a substation requires an insulation system that is essential to it functioning properly. If the insulation system were to be compromised or fail, the HV asset would have to be taken out of service for expensive repairs or maybe even scrapped. Partial discharge (PD) is one of the first indications of a deteriorating insulation system and is the result of localized electrical stress. There are numerous standards that recommend performing PD testing as a method to find issues in an insulation before it compromises the whole system. This leads to the ability to plan outages around those assets seen with critical levels of PD before they result in faults and unscheduled outages.

Partial discharge emits energy in a number of ways and therefore there are several different methods that can be utilized to detect and quantify this energy. For instance, PD can be measured by use of ultra-high frequency (UHF) sensors, transient earth voltage (TEV) sensors, high frequency current transformers (HFCT), and coupling capacitors (CC). Each of these methods provide PD measurements by different means with advantages and limitations based on the application. Moreover, some of these methods are ideal for PD surveying where the objective is to quickly determine if there is the presence of PD in a substation or HV asset, where other methods provide a more in-depth analysis into the type and severity of PD.

This paper will discuss the fundamentals of PD in high voltage assets, the different methods of measuring PD activity, some advantages and limitations of these measurement methods, which methods apply to certain assets, and relevant standards that discuss PD measurements. It is the objective of this paper to provide a basic understanding of PD and which measurement techniques would best be suited for certain field applications. 

  • Practical Approach to Induction Motor Protection Testing 

hester_speaker_photo.pngPRESENTED BY
Abel
González Gómez
Megger

Induction motors are the workhorse of the modern age and they constitute up to 90% of the installed motor base. Motor protection is very important and when done properly can save companies hundreds of thousands of dollars a year in down time.

Modern motor protection devices can monitor all relevant operational variables like line voltages and currents, frequency, speed, temperature, etc. To configure and implement different sets of protection functions using these variables, adequate knowledge of the operational theory of the machine is required. However, proper design and configuration of the motor protection devices and systems is only the first step when it comes to their correct operation. A systematic approach to testing is equally important to detect design flaws, improper configurations, system reliability, and settings changes as well as device malfunctions or failures The ability to create tests that simulate normal as well as faulted motor operating conditions is key to properly evaluating the behavior of the relay.

In this paper a systematic approach for testing the most common induction motor protection functions, is presented. The protection functions presented in the paper are, current and voltage unbalance, under and over voltage, thermal overload, mechanical jam protection, sensitive ground protection, and motor starting elements. A proper approach to testing each of these different motor protection functions will be shared.  

Since proper testing of protection functions starts with the right understanding of their operation, the reasons behind the existence and the theory of operation of each of the motor protection functions is presented as well as how their settings can be related to the motor’s nameplate information. 
Testing motor protection is a very involved and work-intensive process that can become very complicated if it is not well prepared with basic information to get started as in motor nameplate information, settings files in the relays’ proprietary format, and drawings of the protection scheme for the protective relay under test. As previously mentioned, a review of a typical process will be covered to help outline what a technician might need to do in the field.

  • Risk Assessments and the Risk Management Process

hester_speaker_photo.pngPRESENTED BY
Stephen Hester
Saber Power Field Services, LLC

Safety and profitability both depend on how reliable your equipment is. Reliability is a competitive advantage; the costs resulting from an accident or unplanned downtime caused by poor equipment reliability can hit your company hard and affect your bottom line. Since people and equipment represent a substantial capital investment, it only makes sense to keep your equipment in optimum condition. Maintaining reliability and safety requires proper operation, regular inspection and maintenance to detect problems before they interrupt production. Equipment reliability refers to the activities required to sustain the equipment from commissioning through its life expectancy. While the process can be expensive, the benefits come from increased uptime, sustained production and higher profitability. This presentation will examine the various aspects of reliability management, including how sound preventive and predictive maintenance practices can help you and your customers reduce the risks of failure and maintain a safe operating environment for your employees.

  • Safety Performance and the Correlation to Corporate Profitability as a Contractor in the High Voltage Utility Sector

hester_speaker_photo.pnghester_speaker_photo.pngPRESENTED BY
Justin Palmer and Luke Bendon
GasQuip

 

  • Testing Protection Systems in the Real World: Challenges and Recommendations 

hester_speaker_photo.pngPRESENTED BY
Guillermo Falquez
Megger

Protection systems require extensive testing to ensure they operate as intended to protect the power system. Testing protection systems in the real world is a difficult task due to various challenges and situations that you might encounter. Those range from testing for commissioning or maintenance during a shutdown to testing and performing functional checks on equipment in a substation while it is energized. Do you have the substation one-line drawings, or do you have to figure out the connections yourselves? Are you testing a microprocessor relay or an electromechanical relay? Is the substation main locked out and tagged out so that testing can be performed safely? There are a series of questions that need to be answered in order to validate real world protection systems effectively, safely and in a timely manner.

This paper sheds light on various aspects of real-world testing such as challenges faced during testing of specific protection functions, substation one-line drawings, test switches, wiring checks, types of relays used in the implementation of protection schemes, test protocols and requirements, relay settings, testing standards, and safety protocols. Challenges associated with these aspects could differ depending on the type of testing being performed such as commissioning or maintenance testing. Real-world examples for these topics are presented in this paper along with suitable recommendations to overcome those challenges. Finally, a summary is provided that includes tricks and tips that could be beneficial for real-world testing of protection systems. This paper aims to provide a good overview of generic issues faced during real-world testing situations, which will help technicians gain adequate knowledge to handle such situations efficiently.

  • Transformer Insulation Condition Assessment: The Evolution of Diagnostic Testing

hester_speaker_photo.pngPRESENTED BY
Jason Aaron
Megger

Transformers in power distribution and transmission substations play a vital role and must function properly in order to avoid equipment damage or costly unscheduled system outages. Various international standards recommend performing several diagnostic tests in order to assess a transformers condition and possibly identify issues before they cause a fault. Several Of these diagnostic tests are designed to determine the condition of the transformer insulation system which plays a vital role by providing the electrical separation between the windings. A compromised insulation system can quickly lead to a transformer failure or even end of life.

One of the first tests used to determine the condition of an insulation system was DC insulation resistance. The insulation resistance test was first possible in the late 1800’s and allowed for the condition assessment of transformer insulation systems. There are several variants to the insulation resistance test, such as the spot test, time-resistance test method, step voltage test, and others that can be utilized for trending a decay in insulation resistance values that may indicate an issue with the insulation system.

Another valuable diagnostic test to assess the condition of transformer insulation systems is power factor at line frequency (PFLF), a standard test for assessment of liquid immersed apparatus. PFLF is a method to determine the overall condition of a transformers insulation system, where an increase in trending results indicates a deteriorating insulation system. Although beneficial, PFLF has limitations such as low sensitivity in the early stages, lack of data, and inaccurate temperature correction that may lead to an incorrect assessment or an inconclusive analysis.

More advanced diagnostic tests, Narrow Band Dielectric Frequency Response (NBDFR) and Dielectric Frequency Response (DFR), can be performed to offer in-depth analysis into a transformer's insulation condition. These techniques expand power factor measurements beyond line frequency, resulting in multiple power factor measurements across a spectrum of frequencies. This paper will discuss in detail transformer insulation testing, ranging from tests such as DC insulation resistance to advanced diagnostic techniques like NBDFR and DFR. It will cover the theory and benefits behind each measurement, as well as relevant standards defining the acceptance criteria used to evaluate test results.

  • What Happens When a Grounded Transformer is Left Ungrounded? Case Scenario and Protection Considerations

hester_speaker_photo.pngPRESENTED BY
Alex Rangel
Saber Power Field Services, LLC

Large transformers are typically protected primarily by transformer differential protection (87). Although differential protection is outstanding at detecting and clearing internal faults at a fast speed, there are certain power systems conditions that will not be detected by this element. This paper provides the analysis of an event that happened on a 138 kV / 35 kV transformer being fed by solar inverters, in which the neutral connection (X0) was left disconnected by mistake after transformer testing and it caused extensive damage to the lightning arrestors, and how enabling overvoltage (59) protection could have avoided this situation.

  • Winding Condition Assessment of Transformers

hester_speaker_photo.pngPRESENTED BY
Daniel Carreno-Perez
Megger

Transformers are a crucial link in any power  system. When one fails, it can have long lasting ramifications on the power system it is connected to. One of the essential parts of extending the life of a transformer as much as possible, while ensuring proper performance during service, is maintaining its windings in optimal conditions. A full assessment of a transformer windings ’ condition in the field can be done using several  tests. The conductor resistance and connections to the bushings and tap changers can be assessed with winding resistance and transformer turns ratio (TTR); the geometry of the windings is evaluated with capacitance measurements, as well as leakage reactance and sweep frequency response analysis (SFRA); and a comprehensive insulation study can be done using tools such as TTR, excitation current, power factor, insulation resistance, dielectric frequency response (frequency domain spectroscopy), among others.

Understanding how those pieces fit together and how to interpret the data they provide allows to determine the condition of that piece of equipment, as well as to develop a thorough transformer maintenance plan. This paper will focus on understanding the results from the aforementioned tests. Knowing how to interpret individual results, perform trending, and understanding the correlation between these measurements is extremely important, both when assessing the overall condition of the windings as well as troubleshooting issues when unexpected values are obtained.